Maximum Clearance Between Air Inlet and Outlet

Suitability for 50 and 60Hz

Protection Class by Panel

Standard Controller

Ease of Installation

Auto Restart Function

Technicial Specifications
Product Documentation
MODEL BT 2000BT 2000 OD
Cover Galvaniz - InoxGalvaniz - Inox
DIN 3168 Cooling capacity L35 L35Watt20202020
DIN 3168 Cooling capacity L35 L50Watt16301630
Operating VoltageV/hz220-230/50-60220-230/50-60
Starting CurrentA25,925,9
Operating CurrentA4,34,3
FuseA2525
DIN 3168 Power Consumption L35 L35Watt832832
DIN 3168 Power Consumption L35 L50Watt929929
Max. PressureBAR2626
Size : Height/Width/Depthmm1000*405*2301000*405*250
Packaged Size : Height/Width/Depthmm1050*455*2801050*455*280
Net WeightKg4647
Gross WeightKg4851
Max. Air Volume Internal Circuitm³/h945945
Max. Air Volume Exernal Circuitm³/h11751175
Refrigerant R134aR134a
Operational range°C0…..+550…..+55
Protection Category IP to IEC 60 529 (Internal circuit) IP 54IP 65
Protection Category IP to IEC 60 529 (Exernal circuit) IP 34IP 34
Mounting Method WALL MOUNTEDWALL MOUNTED
Color(*)RAL 7035/INOXRAL 7035/INOX
Sound LeveldBA7373
Thermostat setting°C+35+35
EER (Energy Efficiency Rating)EER2,422,42